2
Product & Equipment Quickfinder
Reset All
sectionNumber
Power Solution
13261
Industrial
13361
Mobile
12344
Portable
2000 kW
Diesel Generators / 2000REOZMD


Features
- KOHLER Co. provides one-source responsibility for the generating system and accessories.
- The generator set and its components are prototype-tested, factory-built, and production-tested.
- The 60 Hz generator set offers a UL 2200 listing.
- The generator set accepts rated load in one step.
- The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
- A standard one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.
Alternator features:
- The pilot-excited, permanent-magnet (PM) alternator provides superior short-circuit capability.
- Additional alternator voltages are available including 12.47 kV, 13.2 kV, and 13.8 kV medium voltages. Contact your local distributor for details.
- The brushless, rotating-field alternator has broad range reconnectability.
- NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
- Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
- Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
- Self-ventilated and drip-proof construction.
- Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
- Digital solid-state, volts-per-hertz voltage regulator with ±0.25% no-load to full-load regulation.
- Brushless alternator with brushless pilot exciter for excellent load response.
Other features:
- KOHLER-designed controllers for one source system integration and remote communication.
- The low coolant level shutdown prevents overheating (standard on radiator models only).
- An electronic, isochronous governor delivers precise frequency regulation.
- Multiple circuit breaker configurations.


Specifications
Prime Ratings: | ![]() |
1820 kW (2275 kVA) |
![]() |
||
Standby Ratings: | ![]() |
2000 kW (2500 kVA) |
![]() |
||
Hertz: | ![]() |
60 Hz |
![]() |
||
Alternator Type: | ![]() |
Brushless, Permanent-Magnet Pilot Exciter |
![]() |
||
Generator weights and dimensions | ![]() |
|
Length: | ![]() |
6790 (267.3) |
Width: | ![]() |
2426 (95.5) |
Height: | ![]() |
2602 (102.4) |
Weight, wet: | ![]() |
15422 (34000) |
![]() |
||
EPA Tier Level: | ![]() |
2 |
![]() |
||
Engine Manufacturer: | ![]() |
Mitsubishi |
![]() |
||
Engine Model: | ![]() |
S16R-Y2PTAW2-1 |
![]() |
||
Cylinder Arrangement: | ![]() |
16-V |
![]() |
||
Max Power at Rated RPM: | ![]() |
2180 kWm (2923 BHP) |
![]() |
||
Prime Fuel Consumption at | ![]() |
|
100% load: | ![]() |
536 Lph (141.6 gph) |
75% load: | ![]() |
403 Lph (106.6 gph) |
50% load: | ![]() |
271 Lph (71.6 gph) |
25% load: | ![]() |
154 Lph (40.6 gph) |
![]() |
||
Standby Fuel Consumption at | ![]() |
|
100% load: | ![]() |
606 Lph (160.1 gph) |
75% load: | ![]() |
442 Lph (116.8 gph) |
50% load: | ![]() |
299 Lph (79.0 gph) |
25% load: | ![]() |
164 Lph (43.2 gph) |
![]() |