Download PDF Print Page E-mail Page

760 kW

Enclosures / 750REOZMD

Return to Results
FeaturesSpecifications
  • KOHLER Co. provides one-source responsibility for the generating system and accessories.
  • The generator set and its components are prototype-tested, factory-built, and production-tested.
  • The 60 Hz generator set offers a UL 2200 listing.
  • The generator set accepts rated load in one step.
  • The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
  • A standard one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.

Alternator features:
  • The pilot-excited, permanent-magnet (PM) alternator provides superior short-circuit capability.
  • Additional alternator voltages are available including 12.47 kV, 13.2 kV, and 13.8 kV medium voltages. Contact your local distributor for details.
  • The brushless, rotating-field alternator has broad range reconnectability.
  • NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
  • Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
  • Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
  • Self-ventilated and drip-proof construction.
  • Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
  • Digital solid-state, volts-per-hertz voltage regulator with ±0.25% no-load to full-load regulation.
  • Brushless alternator with brushless pilot exciter for excellent load response.

Other features:
  • KOHLER-designed controllers for one source system integration and remote communication.
  • The low coolant level shutdown prevents overheating (standard on radiator models only).
  • An electronic, isochronous governor delivers precise frequency regulation.
  • Multiple circuit breaker configurations.
FeaturesSpecifications
Prime Ratings: 690 kW (863 kVa)
Standby Ratings: 760 kW (950 kVa)
Hertz: 60 Hz
Alternator Type: 4-Pole, Rotating-Field, Brushless, Permanent-Magnet Pilot Exciter
Generator weights and dimensions
Length: 4968 (195.6)
Width: 1854 (73)
Height: 2419 (95.2)
Weight, wet: 6577 (14500)
EPA Tier Level: 2
Engine Manufacturer: Mitsubishi
Engine Model: S12A2-Y2PTAW-2
Cylinder Arrangement: 12-V
Engine RPM: 1800RPM
Max Power at Rated RPM: 900 kWm (1207 BHP)
Prime Fuel Consumption at
100% load: 207.1 Lph (54.7 gph)
75% load: 148.2 Lph (39.2 gph)
50% load: 99.8 Lph (26.4 gph)
25% load: 61.8 Lph (16.3 gph)
Standby Fuel Consumption at
100% load: 232.3 Lph (61.4 gph)
75% load: 164 Lph (43.3 gph)
50% load: 108.2 Lph (28.6 gph)
25% load: 65 Lph (17.2 gph)
FeaturesSpecificationsOptions