Download PDF Print Page E-mail Page

105 kW

Enclosures / 100REOZJ4

Return to Results
FeaturesSpecificationsOptions
  • KOHLER Co. provides one-source responsibility for the generating system and accessories.
  • The generator set and its components are prototype-tested, factory-built, and production-tested.
  • The 60 Hz generator set offers a UL 2200 listing.
  • The generator set accepts rated load in one step.
  • The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
  • Tier 4 Final EPA-Certified for Stantionary Emergence and Non-Emergency Applications
  • A one-year limited warranty covers all systems and components. Two- and five-year extended warranties are also available.

Alternator features:
  • NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting
  • Capable of sustained line-to-neutral short circuit current of up to 300% of the rated current for up to 2 seconds. Capable of sustained short circuit current of up to 300% of the rated current for up to 10 seconds for 3 phase connections. (IEC 60092-301 short-circuit performance.)
  • Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field.
  • Self-ventilated and dripproof construction
  • Vacuum-impregnated windings with epoxy varnish for dependability and long life.
  • Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
  • Windings are vacuum-impregnated with epoxy varnish for dependability and long life.
  • Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
  • The unique Fast-Response(R) X excitation system delivers excellent voltage response and short-circuit capability using a rare-earth, permanent magnet (PM)-excited alternator.

Engine features:
  • One-side serviceability of fuel system, lubrication system, and air cleaner

Other features:
  • KOHLER-designed controllers for guaranteed system integration and remote communication.
  • The low coolant level shutdown prevents overheating.
  • Durable steel-sound attenuating housing with quiet operation of 71 dB(A) log average @7 m (23 ft.) with full load at the prime rating.
  • Stainless steel hinges and lockable latches on doors.
  • 125% environmental containment basin for oil and coolant.
  • 110% secondary containment tank for fuel
  • UL 142 listed subbase fuel tank for 24-hour run time with full load at prime rating (minimum).
  • Fuel fill and Diesel Exhaust Fluid (DEF) fill with lockable caps.
  • Customer connection panel with main circuit breaker, remote start connection, and emergency stop switch.
FeaturesSpecificationsOptions
Prime Ratings: 96 kW (120 kVa)
Standby Ratings: 105 kW (131 kVa)
Hertz: 60 Hz
Alternator Type: 4-Pole, Rotating-Field,Brushless, Rare-Earth, Permanent-Magnet
Generator weights and dimensions
Length: 2951 (116.2)
Width: 1119 (44.1)
Height: 2156 (84.9)
Weight, wet: 2660 (5864)
EPA Tier Level: 4 Final
Engine Manufacturer: John Deere
Engine Model: 4045HFG09
Cylinder Arrangement: 4 Inline
Engine RPM: 1800RPM
Max Power at Rated RPM: 124 kWm (166 BHP)
Fuel Capacity in Gallons: 192
Prime Fuel Consumption at
100% load: 28 Lph (7.4 gph)
75% load: 21.2 Lph (5.6 gph)
50% load: 15.4 Lph (4.1 gph)
25% load: 9.8 LPh (2.6 gph)
Standby Fuel Consumption at
100% load: 30.8 Lph (8.1 gph)
75% load: 22.9 Lph (6.0 gph)
50% load: 16.3 Lph (4.3 gph)
25% load: 10.4 Lph (2.7 gph)
FeaturesSpecificationsOptions

Accessories

  • The generator set engine is certified by the Environmental Protection Agency (EPA) to conform to Tier 4 Final nonroad emissions regulations.
  • The unique Fast-Responser X excitation system delivers excellent voltage response and short-circuit capability using a rare-earth, permanent magnet (PM)-excited alternator.
  • The brushless, rotating-field alternator has broadrange reconnectability.
  • Remote control connector
  • Class H insulation
  • Reconnectable voltage
  • One- or three-phase reconnectable alternator
  • Heat exchanger cooled configuration includes a wet exhaust bend
  • Keel cooled configuration includes a dry exhaust bend