30 kW

Enclosures / 30CCL

FeaturesSpecificationsOptions
  • KOHLER Co. provides one-source responsibility for the generating system and accessories.
  • The generator set and its components are prototype-tested, factory-built, and production-tested.
  • A one-year limited warranty covers all generator set systems and components. Two- and five-year extended limited warranties are also available.

Alternator features:
  • NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting
  • Capable of sustained line-to-neutral short circuit current of up to 300% of the rated current for up to 2 seconds. Capable of sustained short circuit current of up to 300% of the rated current for up to 10 seconds for 3 phase connections. (IEC 60092-301 short-circuit performance.)
  • Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field.
  • Self-ventilated and dripproof construction
  • Vacuum-impregnated windings with epoxy varnish for dependability and long life.
  • Superior voltage waveform from a two-thirds pitch stator and skewed rotor.

Engine features:
  • One-side serviceability of fuel system, lubrication system, and air cleaner

FeaturesSpecificationsOptions
Prime Ratings: NA (NA)
Standby Ratings: 30 kW (38 kVa)
Hertz: 60 Hz
Alternator Type: Brushless, Wound-Field
Generator weights and dimensions
Length: 2280 (89.8)
Width: 830 (32.7)
Height: 1182 (46.5)
Weight, wet: 635 (1400)
EPA Tier Level: 4i
Engine Manufacturer: Kohler
Engine Model: KG2204T
Cylinder Arrangement: 4 Inline
Engine RPM: 1800RPM
Max Power at Rated RPM: 47.8 kWm (64.1 BHP)
Standby Fuel Consumption at
100% load: 4.6 m³/hr. (164 cfh)
75% load: 3.7 m³/hr. (131 cfh)
50% load: 2.8 m³/hr. (99 cfh)
25% load: 1.9 m³/hr. (66 cfh)
FeaturesSpecificationsOptions

Accessories

  • Engine is Environmental Protection Agency (EPA)-certified
  • Class H insulation
  • The brushless, rotating-field alternator has broadrange reconnectability
  • Remote control connector
  • Class H insulation
  • Reconnectable voltage
  • One- or three-phase reconnectable alternator
  • Heat exchanger cooled configuration includes a wet exhaust bend
  • Keel cooled configuration includes a dry exhaust bend